The Power Line Out of Climax Isn't Built for What's Coming. A $250 Million Fix Heads to ERCOT's Board.

Collin County Roads & Infrastructure

The Power Line Out of Climax Isn't Built for What's Coming. A $250 Million Fix Heads to ERCOT's Board.

ERCOT's Technical Advisory Committee endorsed Texas-New Mexico Power's $249.8 million Climax to Bells transmission project, which would upgrade the Climax-to-Blue Ridge line in Collin County to 138 kilovolts.

Interactive mode

See this story, step by step.

The same reporting, built as you scroll. Go at your own pace.

The power line that runs from Climax to Blue Ridge in northeast Collin County was built to carry a fraction of what the area is expected to need. A $249.8 million plan to rebuild it, along with the lines beyond it, is now headed to the board of the Electric Reliability Council of Texas.

ERCOT's Technical Advisory Committee, a panel of power industry and consumer representatives that reviews grid decisions before they reach the board, endorsed the Texas-New Mexico Power project on Nov. 18 as part of a five-item package that passed unanimously. The project would upgrade about 40 miles of lines between Climax and Bells in Grayson County and rebuild a separate 26-mile line with wiring that dates to the 1930s.

Why the Climax line needs more room

The project starts in Climax, an unincorporated community in Collin County. TNMP, which submitted the project in April, proposed moving the Climax end of the existing line to the Thistle 138-kilovolt substation and upgrading the roughly 7.3 miles to Blue Ridge to run at 138 kilovolts instead of 69. That would raise the line's rating, a measure of how much power it can carry, from 36 megavolt-amperes to at least 383, more than 10 times as much.

The reason is growth. ERCOT's planning documents say the project is meant to fix "thermal overloads and voltage violations due to load growth in Grayson and Collin counties." In plain terms, as the area draws more power, lines would carry more electricity than they are rated for, and voltage would drift outside acceptable limits. ERCOT's study, built on expected summer 2030 peak demand and including new loads in the Climax area, found nine overloads and 11 voltage problems. The new customers have not been named in ERCOT's public documents.

"Basically it's a reliability project," ERCOT's presenter told the committee.

From Blue Ridge, the upgrades continue about 32.5 miles through Leonard, Trenton and Whitewright to Bells. TNMP's proposal also included two new substations, one about 3 miles from Leonard and one about 3.5 miles from Bells.

Why ERCOT picked the pricier plan

ERCOT looked at four options and narrowed them to two. Option 4 would have cost $180.7 million. ERCOT recommended Option 1 at $249.8 million because it adds a roughly 26-mile segment the presenter described as aging infrastructure, "with conductors going back to like" the 1930s.

That segment accounts for roughly $70 million to $80 million of the difference, according to ERCOT, but it replaces old equipment and avoids the added congestion Option 4 would have created. Congestion happens when lines cannot carry all the power that is available, which can force the grid to lean on more expensive generation.

The price has also climbed since TNMP first filed. The original estimate was $225.4 million. When a representative of the Office of Public Utility Counsel, the state agency that represents residential and small business customers, asked about the increase, ERCOT said the estimates were updated because the work involves both TNMP and Oncor.

ERCOT's board takes it up next

ERCOT said it will recommend Option 1 to its board, and its planning documents set December 2026 as the target for board endorsement. ERCOT says the project will not need a certificate of convenience and necessity, the Public Utility Commission approval typically required for new transmission lines. TNMP estimates the work would be finished by December 2030, a year later than the date in ERCOT's earlier documents.